AXISA1001NetworkDoorController
ReaderI/OConnector
6-pinterminalblockfor:
Auxiliarypower(DCoutput)
DigitalInput
DigitalOutput
0VDC(-)
FunctionPinNotes
Specications
0VDC(-)
1
0VDC
DCoutput
2
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedas
powerout.
12VDC
Maxload=300mA
DigitalinputConnecttopin1to
activate,orleaveoating(unconnected)
todeactivate.
0tomax40VDC
Congurable
(Inputor
Output)
3–6
DigitaloutputConnectedto
pin1whenactivated,oating
(unconnected)whendeactivated.If
usedwithaninductiveload,e.g.arelay,
adiodemustbeconnectedinparallel
withtheload,forprotectionagainst
voltagetransients.
0tomax40VDC,open
drain,100mA
DoorConnector
Two4-pinterminalblocksfordoormonitoringdevices(digitalinput).
FunctionPinNotes
Specications
0VDC(-)
1,3
0VDC
Input
2,4
Forcommunicatingwithdoormonitor.
DigitalinputConnectto
pin1or3respectivelytoactivate,
orleaveoating(unconnected)to
deactivate.
Note:Thispincanonlybeusedfor
input.
0tomax40VDC